Technical parameters :
The inlet temperature: 38 ℃, the highest rated 45 ℃
Pressure: rated 0.7 Mpa, 4.5 Mpa, accept the order under 0.3-0.95 Mpa permitted.
Environmental temperature: air-filled type (A) : ≥ 2 ℃; ,≤38 ℃, Water-cooling (W):≥2℃,≤45℃
Pressure dew point: 2-10℃(0.7Mpa)
Cooling water temperature: t into ≤31℃ t out ≤37℃
Cooling water pressure: 0.15-0.4Mpa
Installation: indoor, without foundation, concrete floor peripheral blank not less than the 1-m
Product standards: JB/JQ209010-88 "freezing dryer technical conditions"